Chapter 4
Mechanical and Electrical Installation
LCL filter with one line side converter.
80
6. Disconnect the PDI and CTL fiber-optic cables, if present, from the
power layer interface circuit board.
Figure 42 - Power Module PDI and CTL Fiber-optic Cable Connections
7. Without bending the cable to a radius less than 50 mm (2 in.), carefully
remove the disconnected fiber-optic cables from the power module
chassis. See
Figure
8. Disconnect any cables, P1 through P4, that are plugged into the I/O
panel in the power module(s). See
Figure 43 - Power Module I/O Panel Connections
P3
9. Carefully remove the disconnected cables from the power module
chassis.
Rockwell Automation Publication 750-IN100B-EN-P - July 2017
LCL filter with two line side converters.
42.
Figure
43.
P1
P4