Table 34 - 22-Series I/O Module TB1 Wiring Examples (continued)
Input/Output
Connection Example
3-Wire Control
Internal supply
3-Wire Control
External 24 volt supply
20-750-2262C-2R
20-750-2263C-1R2T
3-Wire Control
External 120 volt supply
20-750-2262D-2R
24VC
+24V
Stop
Di C
Di 0
Di 1
Start
22-Series I/O Module TB1
+24V
Common
Stop
Di C
Di 0
Di 1
Start
22-Series I/O Module TB1
+120V
Common
Stop
Di C
Di 0
Di 1
Start
22-Series I/O Module TB1
Rockwell Automation Publication 750-IN100B-EN-P - July 2017
Required Parameter Changes
• Set Selection
Port 00:108 [DI M Stop] = Port nn:1 [Dig In Sts], bit 0 = Input 0 (22-Series I/O Module)
Port 00:117 [DI M Start] = Port nn:1 [Dig In Sts], bit 1 = Input 1 (22-Series I/O Module)
• View Results
Port nn:1 [Dig In Sts] (22-Series I/O Module)
Port 10/11:354 [Motor Side Sts 1]
• Set Selection
Port 00:108 [DI M Stop] = Port nn:1 [Dig In Sts], bit 0 = Input 0 (22-Series I/O Module)
Port 00:117 [DI M Start] = Port nn:1 [Dig In Sts], bit 1 = Input 1 (22-Series I/O Module)
• View Results
Port nn:1 [Dig In Sts] (22-Series I/O Module)
Port 10/11:354 [Motor Side Sts 1]
• Set Selection
Port 00:108 [DI M Stop] = Port nn:1 [Dig In Sts], bit 0 = Input 0 (22-Series I/O Module)
Port 00:117 [DI M Start] = Port nn:1 [Dig In Sts], bit 1 = Input 1 (22-Series I/O Module)
• View Results
Port nn:1 [Dig In Sts] (22-Series I/O Module)
Port 10/11:354 [Motor Side Sts 1]
I/O Wiring
Chapter 6