Chapter 6
I/O Wiring
146
ATTENTION: Risk of equipment damage exists. Ensure that the correct
voltage is applied to the I/O Module digital inputs. Refer to the I/O Module
catalog number to determine the voltage rating.
• 20-750-1132C-2R is rated 24 Volts DC
• 20-750-1133C-1R2T is rated 24 Volts DC
• 20-750-1132D-2R is rated 120 Volts AC
Table 25 - TB2 Terminal Designations (2 Relay Outputs: 2R)
Relay Out
Terminal Name
R0NO
Relay 0 N.O.
R0C
Relay 0 Common
R0NO
R0C
R0NC
R0NC
Relay 0 N.C.
R1NO
R1C
R1NC
R1NO
Relay 1 N.O.
R1C
Relay 1 Common
R1NC
Relay 1 N.C.
Table 26 - TB2 Terminal Designations (1 Relay and 2 Transistor Outputs: 1R2T)
Relay Out
Terminal Name
R0NO
Relay 0 N.O.
R0NO
R0C
Relay 0 Common
R0C
R0NC
R0NC
Relay 0 N.C.
T0
TC
T1
T0
Transistor Output 0
TC
Transistor Output
Common
T1
Transistor Output 1
Rockwell Automation Publication 750-IN100B-EN-P - July 2017
Description
Relay Normally Open contact output:
240V AC, 30V DC, 3.5 A max.
General Purpose (Inductive) / Resistive
Relay Normally Closed contact output:
240V AC, 30V DC, 5 A max.
Resistive Only
Description
Relay Normally Open contact output:
240V AC, 24V DC, 3.5 A max.
General Purpose (Inductive) / Resistive
Relay Normally Closed contact output:
240V AC, 24V DC, 5 A max.
Resistive Only
Transistor output
Rating: 24V DC = 1 A max. including U.L.
applications
Resistive
Related
Param
10, 100,
101,
105, 106
on Port
nn
20, 110,
111,
115, 116
on Port
nn
Related
Param
10, 100,
101,
105, 106
on Port
nn
20
on Port
nn
30
on Port
nn