Chapter 5
Power Wiring
Table 12 - PowerFlex 755TL/TR Drive Jumpers
Grounding Scheme
EMC Option
Factory Default
C3
(2)
Grounded
C2
C3
Ungrounded/High-
N/A
(1)
resistance Ground
AC fed ungrounded
Impedance grounded
B phase ground
Marine Ungrounded /
N/A
(1)
High Resistance Ground
(1) Ungrounded and high-resistance ground systems do not meet the EMC Directive due to the disconnected jumper positions.
(2) Rockwell Automation is evaluating the ability to meet Category C2 compliance. Contact the factory for more information.
Table 13 - PowerFlex 755TM Regenerative Bus Supplies Jumpers
Grounding Scheme
EMC Option
Factory Default
C3
(2)
Grounded
C2
C3
Ungrounded/High-
N/A
(1)
resistance Ground
AC fed ungrounded
Impedance grounded
B phase ground
Marine Ungrounded /
N/A
(1)
High Resistance Ground
(1) Ungrounded and high-resistance ground systems do not meet the EMC Directive due to the disconnected jumper positions.
(2) Rockwell Automation is evaluating the ability to meet Category C2 compliance. Contact the factory for more information.
128
ATTENTION: Risk of equipment damage exists. The drive power source type
must be accurately determined. Jumpers PE-A, PE-A1, PE-A2, and PE-B1
must be configured for the power source type according to the
recommendations in the PowerFlex 755T Input Product RF Emission
Compliance and Installation Requirements table on page 30.
PE-A
PE-A1
(MOV on the AC
(MOV in the TVSS
Precharge Control
Module)
Circuit Board)
Connected (In)
Connected (In)
TBD
TBD
Connected (In)
Connected (In)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
PE-A
PE-A1
(MOV on the AC
(MOV in the TVSS
Precharge Control
Module)
Circuit Board)
Connected (In)
Connected (In)
TBD
TBD
Connected (In)
Connected (In)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
Rockwell Automation Publication 750-IN100B-EN-P - July 2017
PE-A2
PE-B1
(Common Mode Caps
(Y-Caps on Line Side
on All AC Common
Converter Power
Mode Filter Circuit
Interface Circuit
Boards)
Boards)
Connected (In)
Disconnected (Out)
TBD
TBD
Connected (In)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
PE-A2
PE-B1
(Common Mode Caps
(Y-Caps on Line Side
on All AC Common
Converter Power
Mode Filter Circuit
Interface Circuit
Boards)
Boards)
Connected (In)
Disconnected (Out)
TBD
TBD
Connected (In)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
(Y-Caps on Motor
Side Inverter Power
Interface Circuit
Boards)
Disconnected (Out)
TBD
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
(Y-Caps on Motor
Side Inverter Power
Interface Circuit
Boards)
N/A
N/A
N/A
N/A
N/A