Allen-Bradley PowerFlex 755T Installation Instructions Manual page 178

Powerflex 750-series products with totalforce control
Hide thumbs Also See for PowerFlex 755T:
Table of Contents

Advertisement

Chapter 6
I/O Wiring
178
Table 64 - Universal Feedback Option Module DIP Switch Settings - Safety Application
Safety Channel Selection
Primary Safety Channel
To connect feedback signals to the Primary Safety Channel, set:
S1 sliders to ON
S2 sliders to OFF
S3 slider to ON
Secondary Safety Channel
To connect feedback signals to the Secondary Safety Channel, set:
S1 sliders to OFF
S2 sliders to ON
S3 slider to ON
Primary and Secondary Safety Channels
To connect feedback signals to both the Primary and Secondary Safety Channels,
set:
S1 sliders to ON
S2 sliders to ON
S3 slider to ON
(1) DIP switches only function when safety channels are used.
Rockwell Automation Publication 750-IN100B-EN-P - July 2017
(1)
DIP Switch Settings
S1 S2 S3
S1 S2 S3
S1 S2 S3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerflex 755tlPowerflex 755trPowerflex 755tm

Table of Contents