Allen-Bradley PowerFlex 755T Installation Instructions Manual page 12

Powerflex 750-series products with totalforce control
Hide thumbs Also See for PowerFlex 755T:
Table of Contents

Advertisement

Chapter 1
Product Overview
1...3
4
5
6
20G
1
D
3
a
b
c
d
f9
PowerFlex 755TM Common Bus Inverter ND Rating
400V, 50 Hz Input
Code
Amps
302
302
367
367
460
460
540
540
585
585
650
650
750
750
770
770
920
920
1K0
1040
1K1
1112
1K2
1175
1K4
1465
1K6
1590
1K7
1715
1000
2K1
2156
1250
2K8
2849
1650
3K5
3542
2000
f11
PowerFlex 755TM Common Bus Inverter ND Rating
600V, 60 Hz Input
Code
Amps
242
242
250
295
295
300
355
355
350
395
395
400
435
435
450
545
545
550
595
580
600
690
690
700
760
760
800
825
825
900
980
980
1000
1K1
1045
1100
1K2
1220
1250
1K5
1430
1500
2K0
1946
2000
2K4
2420
2500
12
Catalog Number Explanation (continued)
7
8...10
11
12
F
2K3
M
N
e
f9...f12
g
h
PowerFlex 755TM Common Bus Inverter ND Rating
kW
Frame
Code
160
302
200
361
250
430
315
505
8
315
545
355
617
400
710
400
740
500
800
560
960
630
9
1K0
710
1K1
800
1K3
850
1K4
10
1K6
2K0
11
2K6
12
3K4
PowerFlex 755TM Common Bus Inverter ND Rating
Hp
Frame
Code
215
265
330
8
370
415
505
565
650
9
735
820
920
1K0
10
1K1
1K4
11
1K8
12
2K3
Rockwell Automation Publication 750-IN100B-EN-P - July 2017
13
14
15
16
17
D
N
N
N
N
i
f10
480V, 60 Hz Input
Amps
Hp
Frame
302
250
361
300
430
350
505
400
8
545
450
617
500
710
600
740
650
800
700
960
800
1045
900
9
1135
1000
1365
1100
1420
1250
1655
1500
10
2072
1800
2738
2400
11
3404
3000
12
f12
690V, 50 Hz Input
Amps
kW
Frame
215
200
265
250
330
315
8
370
355
415
400
505
500
565
560
650
630
735
710
9
820
800
920
900
1030
1000
1150
1100
10
1419
1400
1865
1800
11
2318
2300
12
18
N
-C0-C11-P15...
Control and Power Options
g
Filtering and CM Cap Configuration
CM Cap Default
Code
EMC Filtering
Configuration
J
Yes
Jumper Installed
K
Yes
Jumper Installed
(1)
L
No
Jumper Installed
M
No
Jumper Installed
(1) Jumper is removed when code 20J is selected.
h
(1)
Dynamic Braking
Code
Internal Resistor
Internal Transistor
N
No
(1) Not available on Frames 8...12, specify Code "N."
i
Door Mounted HIM (Frames 8...10)
Code
Operator Interface and Control
No Door Mounted HIM
A
with TotalFORCE Control
Enhanced LCD, Full Numeric, IP66, NEMA Type 4X/12 with
D
TotalFORCE Control
Control Option Selections
Code
Option
Frames
C0
Torque Accuracy Module
8...12
Control Transformer (Internal
C1
8...12
(1)
240V)
C11
Single Pod (with Control Bay)
8...12
C12
Dual Pod (with Control Bay)
8...12
(1) If this option is not selected the 240V source must be
customer supplied.
Power Option Selections
Code
Option
Frames
P15
Top Cable Exit w/wiring bay
8...12
P16
Top Cable Entry w/wiring bay
10...12
P17
Top Cable Entry no wiring bay
8... 9
P46
System DC Bus (4700 Amp)
8...10
P50
DC Bus Conditioner
8...12
Reflected Wave
Filtering
No
Yes
No
Yes
No
Input Type
D, E, F, G
D, E, F, G
D, E
D, E
Input Type
D, E, F, G
F, G
F, G
D, E, F, G
D, E, F, G

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerflex 755tlPowerflex 755trPowerflex 755tm

Table of Contents