L-Bracket Connections
Power cable connections in entry and exit wire bay are made using L-brackets.
The M10 hardware that is required to fasten the L-brackets to the slotted bus
bar is provided. Wires with appropriate barrel lugs can be bolted to both sides
of the L-brackets if necessary. Up to four conductors can be attached to each L-
bracket. Attach the conductors to the L-brackets using M12 or 0.5 in. diameter
bolts, nuts, and washers. Bellville spring washers, or equivalent, are
recommended. Keep the L-bracket connections at least 51 mm (2 in.) away
from the ends of the slotted bus bar.
51 mm
(2 in.)
Cable Connections
Customer-supplied M12 hardware.
M12
19 mm
38 N•m (336 lb•in)
Additional Power Terminal L-Brackets
PowerFlex 755T entry and exit wire bays come equipped with L-brackets. If an
application requires additional L-brackets, kit number 20-750-MLBRKT-
F8M is available. Each kit contains three L-brackets and mounting hardware.
Figure 58 - L-Bracket Approximate Dimensions
110.0 mm
25.5 mm
46.0 mm
(1.81 in.)
(1.04 in.)
85.1 mm
(3.35 in.)
44.5 mm
(1.75 in.)
17.8 mm
(0.70 in.)
Rockwell Automation Publication 750-IN100B-EN-P - July 2017
(4.33 in.)
Ø11.0 mm
(0.43 in.)
Power Wiring
Chapter 5
51 mm
(2 in.)
M10
15 mm
38 N•m (336 lb•in)
109