Allen-Bradley PowerFlex 755T Installation Instructions Manual page 160

Powerflex 750-series products with totalforce control
Hide thumbs Also See for PowerFlex 755T:
Table of Contents

Advertisement

Chapter 6
I/O Wiring
Table 34 - 22-Series I/O Module TB1 Wiring Examples (continued)
Input/Output
Connection Example
Digital Input
PLC Output Module
Control from
Prog. Controller
Digital Output
Internal supply
20-750-2263C-1R2T
Digital Output
External supply
20-750-2263C-1R2T
OR
OR
PLC TB
Table 35 - 22-Series I/O Relay Wiring Examples
Input/Output
Connection Example
Relay Output
22-Series I/O Module
External supply
160
Neutral/
Common
10k Ohm, 2 Watt
DiC
Di0
Di1
22-Series I/O Module TB1
24VC
+24V
T0
TC
T1
22-Series I/O Module TB1
22-Series I/O Module TB2
T0
TC
T1
+24V
Common
PLC
1756-1B16
T0
IN-0
GND-0
TC
T1
+24VDC Common
PLC
1756-1V16
DC-0+
T0
IN-0
TC
T1
+24VDC Common
22-Series I/O Module TB2
R1NO
R1C
R1NC
or
R0NO
R0C
R0NC
Power
Source
Rockwell Automation Publication 750-IN100B-EN-P - July 2017
Required Parameter Changes
• Set Selection
Port 00:108 [DI M Stop] = Port nn:1 [Dig In Sts], bit 0 = Input 0 (22-Series I/O Module)
Port 00:117 [DI M Start] = Port nn: 1 [Dig In Sts], bit 1 = Input 1 (22-Series I/O Module)
• View Results
Port nn:1 [Dig In Sts] (22-Series I/O Module)
Port 10/11:354 [Motor Side Sts 1]
• Set Selection
Port nn:20 [TO0 Sel] (22-Series I/O Module) = Port 10/11:354 [Motor Side Sts 1], bit 7 =
Faulted
• View Results
Port nn:5 [Dig Out Sts]s (22-Series I/O Module)
Required Parameter Changes
• Set Selection
Port nn:10 [RO0 Sel] (22-Series I/O Module) = Port 10/11:354 [Motor Side Sts 1], bit 7 =
Faulted
• View Results
Port nn:5 [Dig Out Sts] (22-Series I/O Module)