Table 14 - PowerFlex 755TM Common Bus Inverter Jumpers
Supply Source
Grounding Scheme
Type
Regenerative
Factory Default
Grounded
Ungrounded/High-
resistance Ground
Marine Ungrounded /
High Resistance
(1)
Ground
Non-Regenerative
Factory Default
(third-party)
Grounded
Ungrounded/High-
resistance Ground
Marine Ungrounded /
High Resistance
(1)
Ground
(1) Ungrounded and high-resistance ground systems do not meet the EMC Directive due to the disconnected jumper positions.
(2) Full compliance requires an optional EMC solution that is mounted in a dedicated enclosure. Rockwell Automation is evaluating the ability to meet Category C2 compliance. Contact the factory for
more information.
EMC
PE-A
Option
(MOV on the AC
Precharge
Control Circuit
Board)
C3
N/A
(2)
C2
N/A
C3
N/A
N/A
N/A
(1)
N/A
N/A
C3
N/A
(2)
C2
N/A
C3
N/A
N/A
N/A
(1)
N/A
N/A
Rockwell Automation Publication 750-IN100B-EN-P - July 2017