Section 6: Troubleshooting
April 2013
6.3.3

Diagnostic message: Advisory

Table 6-4. Status: Advisory
LCD
Alert name
screen
Non-Critical
User Data
Warning
MEMRY
WARN
Sensor
Parameter
Warning
LCD Display
Update Failure
[If display
is not
updating]
Configuration
[none]
Changed
Analog
ANLOG
Output Fixed
FIXED
Simulation
[none]
Active
86
LOI screen Problem
A user written parameter
does not match
expected value.
MEMORY
WARN
A user written parameter
does not match
expected value.
[If display
The LCD Display is not
is not
receiving updates from
updating]
the pressure sensor.
[none]
A recent change has
been made the device by
a secondary HART
master such as a
handheld device.
ANALOG
The analog output is
FIXED
fixed and does not
represent the process
measurement. This may
be caused by other
conditions in the device,
or because the device
has been set to loop test
or multidrop mode.
[none]
The device is in
simulation mode and
may not be reporting
actual information.
Recommended action
1.
Confirm and correct all parameters
listed in Device Information.
2.
Perform a Device Reset.
3.
Replace Electronics Board.
1.
Confirm and correct all parameters
listed in Device Information.
2.
Perform a Device Reset.
3.
Replace pressure sensor.
1.
Check the connection between the
LCD and the circuit board.
2.
Replace the LCD Display.
3.
Replace the electronics board.
1.
Verify that the configuration change
of the device was intended and
expected.
2.
Clear this alert by selecting Clear
Configuration Changed Status.
3.
Connect a HART master such as AMS
Device Manager or similar which will
automatically clear it.
1.
Take action on any other notifications
from the device.
2.
If the device is in loop test, and should
no longer be, disable or momentarily
remove power.
3.
If the device is in multidrop mode and
should not be, re-enable loop current
by setting the polling address to 0.
1.
Verify that simulation is no longer
required.
2.
Disable simulation mode in service
tools.
3.
Perform a Device Reset.