Switching Hart Revision; Switching Hart Revision With Generic Menu; Switching Hart Revision With Field Communicator; Switching Hart Revision With Ams Device Manager - Emerson Rosemount 2051 Reference Manual

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Section 5: Operation and Maintenance
April 2013
5.7

Switching HART Revision

Some systems are not capable of communicating with HART Revision 7 devices. The following
procedures list how to change HART revisions between HART Revision 7 and HART Revision 5.
5.7.1

Switching HART revision with Generic Menu

If the HART configuration tool is not capable of communicating with a HART Revision 7 device, it
should load a Generic Menu with limited capability. The following procedures allow for
switching between HART Revision 7 and HART Revision 5 from a Generic Menu.
1.
a.
b. To change to HART Revision 7, Enter: HART7 in the message field
5.7.2

Switching HART Revision with Field Communicator

From the HOME screen, enter the fast key sequence and follow steps within the Field
Communicator to complete the HART revision change.
From the HOME screen, enter the fast key sequence
Device Dashboard Fast Keys
5.7.3

Switching HART Revision with AMS Device Manager

1.
2.
Note
AMS Device Manager versions 10.5 or greater are compatible with HART Revision 7.
5.7.4

Switching HART revision with Local Operator Interface

Navigate to HART REV within the extended menu and select if either HART REV 5 or HART REV 7.
Use
Figure 5-8
78
Locate "Message" field
To change to HART Revision 5, Enter: HART5 in the message field
Click on Manual Setup and select HART
Select Change HART Revision then follow the on screen prompts.
below to change HART Revision.
Reference Manual
00809-0100-4107, Rev BA
HART5
2, 2, 5, 2, 4
2, 2, 5, 2, 3
Operation and Maintenance
HART7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents