Configuring The Lcd Display - Emerson Rosemount 2051 Reference Manual

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Section 2: Configure
April 2013
2.7

Configuring the LCD Display

The LCD Display configuration command allows customization of the LCD to suit application
requirements. The LCD will alternate between the selected items.
In the following instructions, the LCD can also be configured to display configuration
information during the device startup. Select Review Parameters at Startup to enable or
disable this functionality.
Reference
Configuring LCD Display with a Field Communicator
From the HOME screen, enter the fast key sequence
Device Dashboard Fast Keys
Configuring LCD Display with AMS Device Manager
Right click on the device and select Configure.
1.
Click Manual Setup, select the Display tab.
2. Select desired display options and click Send.
Configuring LCD Display with a Local Operator Interface
Refer to
Figure 2-12. Display with LOI
20
Pressure Units
Sensor Temperature
% of Range
mA/Vdc Output
Scaled Variable
Figure 1-2 on page 4
Figure 2-12
for LCD Display configuration using a LOI.
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
DISPLAY
EXTENDED MENU
EXIT MENU
LCD with Local Operator Interface for image of LCD screen.
DISPLAY
PRESS (on/off)
SCALED (on/off)
TEMP (on/off)
%RANGE (on/off)
ANALOG (on/off)
STRTUP (on/off)
BACK TO MENU
EXIT MENU