Diagnostic Messages - Emerson Rosemount 3051 Manual

Pressure transmitter with 4-20 ma hart protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Manual
00809-0100-4007
6.4 

Diagnostic messages

The following sections contain possible messages that appear on either the display, a
communication device, or an Asset Management Solutions (AMS) system. Use them to
diagnose status messages.
Failure
Function Check
Out of Specification
Maintenance Required
6.4.1 
Diagnostic message: Failure
Electronics Board Failure
A failure has been detected in the electronics circuit board.
Graphical LCD
display
LCD display
Local operator
interface (LOI)
Recommended action
Replace the electronic circuit board.
Sensor Module Failure
A failure has been detected in the sensor module.
Graphical LCD
display
LCD display
Local operator
interface (LOI)
Recommended action
Replace the sensor module.
No Pressure Updates
There are no pressure updates from the sensor to the electronics.
Graphical LCD
display
LCD display
Local operator
interface (LOI)
Recommended actions
Emerson.com/Rosemount
Electronics Board Failure
FAIL BOARD
FAIL BOARD
Sensor Module Failure
FAIL SENSOR
FAIL SENSOR
Sensor Communication Failure
NO P UPDATE
NO PRESS UPDATE
1. Ensure the sensor cable connection to the electronics is tight.
2. Replace the pressure sensor.
Troubleshooting
March 2023
87