Section 4: Electrical Installation
April 2013
4.6

Electrical considerations

Note
Make sure all electrical installation is in accordance with national and local code requirements.
Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical
equipment.
4.6.1

Conduit installation

If all connections are not sealed, excess moisture accumulation can damage the
transmitter. Make sure to mount the transmitter with the electrical housing positioned
downward for drainage. To avoid moisture accumulation in the housing, install wiring with
a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit
connections of the transmitter housing.
Recommended conduit connections are shown in
Figure 4-4. Conduit installation diagrams.
A.
B.
A. Possible conduit line positions
B. Sealing compound
58
Figure
4-4.
B.
A.
Reference Manual
00809-0100-4107, Rev BA
Electrical Installation