Operation Description - Siemens Sitrans LR200 Instruction Manual

Hart
Hide thumbs Also See for Sitrans LR200:
Table of Contents

Advertisement

1.2. Material
Selects the appropriate echo processing algorithms for the material (see Position
Detect (2.8.4.2.) on page 87 for more detail).
Options
a)
dK < 3.0
1.3. Response Rate
Sets the reaction speed of the device to measurement changes in the target range.
Options
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater).
1.4. Units
Sensor measurement units.
Options
1.5. Operating Mode
Space
Level
1)

Operation Description

NO
SERVICE
LEVEL
SPACE
DISTANCE
a)
See Material Level (2.5.1.) on page 79 for more detail.
1)
The point from which High and Low Calibration points are referenced: see
sions: Uni-Construction Polypropylene Rod Antenna
Flange Adapter Versions
7ML19985JP02
SITRANS LR200 (HART) – INSTRUCTION MANUAL
LIQUID
a)
LIQUID LOW DK
(low dielectric liquid – CLEF
Response Rate (2.4.1.)
SLOW
MED
FAST
M, CM, MM, FT, IN
Distance
Measurement and associated loop cur-
rent are not updated, and the device
defaults to Fail-safe mode
Distance to material surface
on page 150.
algorithm enabled
Fill Rate (2.4.2.)/Empty rate (2.4.3.)
0. 1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
High Cal. Point
(process full
level)
Reference point
a)
.
Low Calibration Point
High Calibration Point
Sensor Reference Point
on page 13 and
)
1)
sensor reference point
Low Cal. Point
(process empty level)
Dimen-
Appendix G:
Page 33