Loop-Test; Configuration Flag Reset; Master Reset; Wear - Siemens Sitrans LR200 Instruction Manual

Hart
Hide thumbs Also See for Sitrans LR200:
Table of Contents

Advertisement

Loop-Test

Note: The simulated AO (Analog Output) value influences output to the control system.
Allows you to input a simulated value (4 mA, 20 mA, or a user-defined value) in order to
test the functioning of the mA connections during commissioning or maintenance of the
device. (The range is 3.56 mA: see
To simulate a user-defined mA value:
1)
Open the menu Device – Loop-Test.
2)
Select Other, enter the new value, and click on OK. The message 'Field Device fixed
at [new value]' appears. Click on OK. The Loop-Test window remains open.
3)
When you are ready to end simulation, select End and click on OK to return the
device to the actual output value.

Configuration Flag Reset

To reset the configuration flag to zero, open the menu Device – Configuration Flag Reset and
perform a reset.

Master Reset

Factory Defaults
Use Factory Defaults to reset all user parameters to the default settings, with certain
exceptions. The list of exceptions includes, but is not limited to, Tag, Message,
Description, Installation Data, Device Address, Write Protect and PIN to Unlock. Auto
False Echo Suppression Range and the learned TVT also remain unchanged.
1)
Open the menu Device – Master Reset and click on OK to perform a reset to Factory
Defaults.
2)
After the reset is complete upload parameters to the PC/PG. (If you are performing a
reset after replacing the device with a different instrument, do not upload
parameters to the PC/PG).

Wear

Reports the number of hours the device has been operating, and the number of times it
has been powered up.
Open the menu Device – Wear to view:
Powered Days
Power-on Resets

HART Communication

Allows you to set the number of request/response preambles (minimum 5).
Open the menu Device – HART Communication.

Diagnostics

You can monitor level/volume trends, electronics temperature, and device status.