Application With Stillpipe - Siemens Sitrans LR200 Instruction Manual

Hart
Hide thumbs Also See for Sitrans LR200:
Table of Contents

Advertisement

Application with Stillpipe

A stillpipe is recommended for products with a dK of less than 3, or if extremely turbulent or
vortex conditions exist. This mounting arrangement can also be used to provide optimum
signal conditions on foaming materials.
Notes:
• Near Range (2.8.1.) (Blanking) will be set at the factory. Check the Process Device Tag for
specific values.
• Suitable pipe diameters are 40 mm (1.5") to 100 mm (4").
• The pipe diameter must be matched with the horn size. Use the largest horn size that will
fit the stillpipe/bypass pipe (see
Mounting on a Stillpipe or Bypass Pipe
• See
This application is to obtain a level measurement and corresponding 4 to 20 mA output
proportional to the oil level in a fuel storage vessel.
• Low Calibration Pt. is 5 m (16.5 ft)
from the sensor reference point.
• High Calibration Pt. is 0.5 m (1.65 ft)
from the sensor reference point.
• The stillpipe inside diameter is
50 mm (1.96").
• The maximum rate of filling or
emptying is about 0. 1 m (4")/min.
Parameter
Parameter No./Name
type
Material (1.2.)
Response Rate (1.3.)
Units (1.4.)
Quick Start
Operating Mode (1.5.)
Wizard
Low Calibration Point (1.6.)
High Calibration Point (1.7.)
Apply? (Apply changes) (1.8.)
Page 144
SITRANS LR200 (HART) – INSTRUCTION MANUAL
Flanged Horn dimensions
on page 18 for installation guidelines.
sensor
reference
point
High
Cal.
Pt.
5 m
Low
Cal.
Pt.
Options/
Values
LIQUID LOW DK
MED
M
LEVEL
5
0.5
YES
on page 154).
vent hole
0.5 m
50 mm I.D.
Function
Medium =1 m/minute
meters
Level is reported as Volume
when a vessel shape is
selected.
5 m (16.5 ft)
0.5 m (1.64 ft)
Transfers Quick Start settings to
device.