General Fault Codes

Notes:
• If more than one fault is present, the device status indicator and text for each fault
alternate at 2 second intervals.
• Some faults cause the device to go to Fail-safe mode (Fault 52). These are indicated with
an asterisk (*).
General Fault Codes
Code /
Meaning
Icon
The device was unable to get a measure-
ment within the Fail-safe LOE Timer period.
S: 0
Possible causes: faulty installation,
*
antenna material buildup, foaming/other
adverse process conditions, invalid calibra-
tion range.
S: 2
Unable to collect profile because of a
*
power condition that is outside the operat-
ing range of the device.
S: 3
Device is nearing its lifetime limit according
to the value set in Maintenance Required
Limit.
7ML19985JP02
Meaning (cont' d )
• Data exchanged
• No data exchange
• Write access enabled
• Write access disabled
SITRANS LR200 (HART) – INSTRUCTION MANUAL
Corrective Action
• Ensure installation details are correct.
• Ensure no antenna material buildup.
Clean if necessary.
• Adjust process conditions to minimize
foam or other adverse conditions.
• Correct range calibration.
• If fault persists, contact your local Sie-
mens representative.
Repair required: contact your local Sie-
mens representative.
Replacement is recommended.