warninglimit: Warning temperature threshold in Celsius degrees. The value ranges from 70°C to 85°C
(158°F to 185°F).
alarmlimit: Alarming temperature threshold in Celsius degrees. The value ranges 87°C to 102°C
(188.6°F to 215.6°F). If you do not specify this argument, the last alarming temperature setting applies.
Description
Use the temperature-limit command to set the temperature thresholds for a temperature sensor.
Use the undo temperature-limit command to restore the default.
Table 34 Default temperature thresholds
Card
MPUs, LPUs
When the temperature of a sensor drops below the low temperature threshold or reaches the warning
threshold, the system logs the event and outputs a log message and a trap.
When the temperature of a sensor reaches the alarming threshold, the system constantly outputs log and
tap messages.
NOTE:
The warning and alarming thresholds must be higher than the low temperature threshold.
The alarming threshold must be higher than the warning threshold.
Related commands: display environment.
Examples
# In standalone mode, set the low temperature threshold to –5°C (23°F), the warning threshold to 70°C
(158°F), and the alarming threshold to 100°C (212°F) for hotspot sensor 1 on the card in slot 1.
<Sysname> system-view
[sysname] temperature-limit slot 1 hotspot 1 -5 70 100
time at
Syntax
time time-id at time date command command
time time-id { one-off | repeating } at time [ week-day week-daylist | month-date month-day ] command
command
undo time time-id
View
Job view
Default level
3: Manage level
Sensor
Sensor ID
type
hotspot
1
Low
Warning
temperature
temperature
threshold
threshold
0°C (32°F)
80°C (176°F)
205
Alarming
temperature
threshold
97°C (206.6°F)