Opening Previously Stored Transients; Storing The Trigger - AEMC PowerPad 3945 User Manual

3-phase power quality analyzer
Hide thumbs Also See for PowerPad 3945:
Table of Contents

Advertisement

5.4.1 Opening Previously Stored Transients

The screen below can be accessed with the retrieve
transients previously stored in the memory.
1
2
Œ
The status bar at the top displays the memory fi lled by stored transients.

Name and transient number (from 01 to 50) for each stored transient.
Ž
Transient recording time and date are displayed for each transient.
- To select a transient, press the
button
- To delete a selected transient, press the
button

5.4.2 Storing the Trigger

The threshold T in percent, defi ned as an envelope width (over and under) the last
cycle of signal V or A input signal. Its width W is calculated with the nominal mea-
surement range R for a channel (depending on the selected current sensor).
Example: Using the SR193 probe and a 2% trigger level, the
width would be 1000A x 2% = 20A. Therefore, a deviation of
± 20A will cause a transient event to be captured.
46
SELECTION OF TRANSIENT
TEST 05
TEST 04
TEST 03
TEST 02
TEST 01
07/25/02 10:56
05/07/02 14:31:41
05/07/02 14:31:41
05/07/02 14:31:21
05/07/02 14:31:04
05/07/02 14:31:04
Figure 5-16
buttons, then select it with the
W = T x R
Power Quality Analyzer Model 3945
button. It displays a list
100%
button, then confi rm it with the
3