AEMC PowerPad 3945 User Manual page 46

3-phase power quality analyzer
Hide thumbs Also See for PowerPad 3945:
Table of Contents

Advertisement

The table below lists the capture threshold levels, based on the probe in use (for
the current channels) and voltage at the different percent selections.
MN clamp
SR clamp
AmpFlex™
MR clamp
2999A ratio adapter
1A ratio adapter
Voltage
Transients are detected by comparing all 256 samples on the current cycle with
their counterparts from the previous cycle for each active input channel. Should
any one sample deviate from its counterpart by the selected percentage value in
the set up, this will be considered a transient and the data will be captured.
When capture occurs, four cycles are recorded for each input. These include the
trigger cycle, the previous cycle to the trigger and the two cycles that follow the
triggered cycle. All active inputs will be captured.
Power Quality Analyzer Model 3945
100%
50%
200A
100A
1000A
500A
2900A
1400A
1000A
500A
3000A
1500A
1A
0.5A
480V
240V
Thresholds
20%
10%
40A
20A
200A
100A
580A
290A
200A
100A
600A
300A
0.2A
0.1A
96V
48V
5%
2%
10A
4A
50A
20A
140A
58A
50A
20A
150A
60A
0.05A
0.02A
24V
9.6V
1%
2A
10A
29A
10A
30A
0.01A
4.8V
45