3.10.2 Specifi cations
Range:
Output / Input Ratio:
Dimensions:
Weight:
Impermeability:
Electrical safety:
Operating Temperature: 5° to 131°F (-15° to 55°C), 10 to 90% RH
Storage Temperature:
Reference Conditions:
Current measurement according to IEC 44-1 Class 0.5
Range
Error %
Phase Error
Primary Voltage Loss:
Permanent Overload:
Temperature Infl uence: < 0.1% par 25K
Frequency Infl uence
Error
Phase error
Power Quality Analyzer Model 3945
(add PowerPad™ accuracy ±0.5% ± 1ct)
5A
0.2mV/mA AC
6.00 x 3.75 x 3.40" (153 x 95 x 86mm)
2 lbs (900g)
IP50 per EN 60529 (electrical IP2X for the terminals)
Double Insulation, Category III 300V
Pollution Degree 2 per IEC 61010-1
-40° to 185°F (-40° to 85°C), 0 to 90% RH
73°F (23°C) ±3K, 50 to 85% RH, 50/60Hz ±2Hz
5mA to 50mA
0.35% + 1.5mA
0.5°
< 0.3V
10A
65Hz to 500Hz
0.1%
0.1°
50mA to 1A
0.25% + 1mA
0.4°
500Hz to 1kHz
0.3%
0.2°
1A to 6A
0.25% + 0.5mA
0.33°
1kHz to 5kHz
0.5%
23