3.7 AC Current Probe MN193 Probe
The MN193 is designed to work with secondary current transformers.
Best accuracy is available when entering the transformer ratio (e.g. 1000/5A)
Nominal Range: 5A and 100A
Measurement Range: 5A: 0.005A to 5A
NOTE: Currents below X on the 5A range and Y on the 100A range will be dis-
played as zero on the PowerPad™ with this probe
Probe Output Signal: 5A: 200mV/A
Maximum Clamping Diameter: 0.8" (20mm)
Safety: NF EN 61010-2-032, 600V, CAT III, POLL 2
Reference Conditions:
Ambient temperature
Humidity
Frequency
Distortion factor
Magnetic fi eld of external origin
Accuracy Specifi cations
NOTE: Add PowerPad™ accuracy ±0.5% ± 1ct
Range: 10mV/A (1V @ 100Arms)
Primary current (in A
Accuracy (% of the output signal)
Phase shift (°)
Overload: 120A continuous
Range: 200mV/A (1V @ 5Arms)
Primary current (in A
Accuracy (% of the output signal)
Phase shift (°)
Overload: 12A continuous
Power Quality Analyzer Model 3945
AC
)
AC
)
5mA to 50mA
AC
≤1.5% ±0.1mA
(with Model 3945)
100A: 0.1A to 100A
AC;
100A: 10mV/A
AC;
73°F (23°C) ± 5°F (3°C)
20 to 75% of RH
<1% without superimposed DC current
<40 A/m (earth's magnetic fi eld)
0.1A to 1A
≤1% ±2mA
≤3.2°
0.05A
≤1.5%
≤6.5°
AC
AC
48 to 65Hz
1A to 120A
≤1%
≤2.2°
0.5A
≤1%
≤5°
≤4.5°
5A
≤1%
≤4°