semaphore KINGFISHER PLUS+ Hardware Reference Manual page 42

Modular rtu
Table of Contents

Advertisement

LED
State
ON
SUPP
OFF
ON
40 ms ON,
LOW
5.0 s OFF
OFF
OUT (Outputs) LEDs
ON
12BP
OFF
ON
5BP
OFF
ON
12AUX
OFF
ON
24AUX
OFF
FAULT LEDs
ON
12BP
OFF
ON
5BP
OFF
ON
12AUX
OFF
ON
24AUX
OFF
Notes:
1
) May keep switching ON and OFF intermittently at a very light or no load (v1.3 only).
2
) May keep switching ON and OFF intermittently at very heavy loads (hardware hick-up
mode).
3
) Short flashes every 2 s may indicate that PS-x2 is trying to detect battery.
4
) Current value given to the Processor Module is negative.
5
) Approximate values.
Hardware Manual Version 7.16
Battery sources current of more than 0.1 A
Battery does not supply current to the PS-x2.
+12V_RAIL voltage has fallen below 11.5 V
Battery Low Shutdown.
+12V_RAIL voltage has raised above 12.4 V
Backplane power is switched ON.
Backplane power is switched OFF (either start-up or shutdown).
Backplane power is switched ON.
Backplane power is switched OFF (either start-up or shutdown).
12VAUX is switched ON.
12VAUX is switched OFF.
24ViAUX is switched ON.
24ViAUX is switched OFF.
Backplane power is switched ON and 12VBP is below 9 V
Backplane power is switched OFF or it is ON and 12VBP is above 9 V
Backplane power is switched ON and 5VBP is below 2 V
Backplane power is switched OFF or it is ON and 5VBP above 2 V
12VAUX is switched ON and it is below 9 V
12VAUX is switched OFF or it is ON and above 9 V
24ViAUX is switched ON and it is below 18 V
module installed).
24ViAUX is switched OFF or it is ON and above 18 V
http://www.servelec-semaphore.com/
Kingfisher Plus+ Hardware Manual
Description
4
to the PS-x2
5
.
5
.
5
.
5
.
5
(or no DC-10 / Option –C
5
.
5
.
5
.
5
.
5
.
5
.
Page 42