14.1.2 IO-2 Module LEDs
14.1.3 IO-2 Specifications
Operating Temperature
Storage Temperature
Humidity
Hot Swap
DIGITAL INPUTS
Rated Voltage
Inputs per Module
Input Characteristics
Input Current
Isolation
Hardware Manual Version 7.16
LED
State
OK
FU
A1-A8
B1-B8
IO-2 Combinational IO Module Specifications
-20 to +70 °C
-40 to +85 °C
5 to 95 % RH (non-condensing)
Yes. Module can be swapped while RTU is running. Hot swap will
not cause a Warm Start. Outputs will be restored within 2
seconds once module is replaced. Inputs will be cleared while
module is removed.
12 to 24 V
AC/DC
8
ON-state Voltage
OFF-state Voltage
ON-state Current
OFF-state Current
ON Response Time
OFF Response Time
4 mA (typical) at rated voltage
3 kV between field and logic
http://www.servelec-semaphore.com/
Kingfisher Plus+ Hardware Manual
Description
OFF
Module fault (no power)
ON
Normal
OFF
Fuse OK
ON
Fuse fail
OFF
Digital input OFF
ON
Digital input ON
OFF
Digital output OFF (open)
ON
Digital output ON (closed)
(can use reverse polarity)
11.5 to 30 V
DC
0 to 4 V
DC
3.2 mA minimum
1 mA maximum
10 ms typical
17 ms typical
maximum