Zone Interlocking Trip Logic [X2]
The following overcurrent protection elements trigger Phase Zone-Interlock trip functions:
1.5 * 51P[1];
50P[1]; and
50P[2].
The following overcurrent protection elements trigger Ground Zone Interlock trip functions:
51X[1];
50X[1];
50X[2];
51R[1];
50R[1], and
50R[2].