Eaton EDR 3000 Installation, Operation And Maintenance Manual page 391

Hide thumbs Also See for EDR 3000:
Table of Contents

Advertisement

Switchgear/Breaker Input States
Name
Description
CinBkr-52a-I
Module Input State: Feed-back signal of the Bkr (52a)
CinBkr-52b-I
Module Input State: Feed-back signal of the Bkr. (52b)
Ready-I
Module Input State: Breaker Ready
Sys-in-Sync-I
State of the module input: This signals has to become true within
the synchronization time. If not, switching is unsuccessful.
Ack TripCmd-I
State of the module input: Acknowledgment Signal (only for
automatic acknowledgment). Module input signal
Interl CLOSE1-I
State of the module input: Interlocking of the CLOSE command
Interl CLOSE2-I
State of the module input: Interlocking of the CLOSE command
Interl CLOSE3-I
State of the module input: Interlocking of the CLOSE command
Interl OPEN1-I
State of the module input: Interlocking of the OPEN command
Interl OPEN2-I
State of the module input: Interlocking of the OPEN command
Interl OPEN3-I
State of the module input: Interlocking of the OPEN command
EDR-3000
www.eaton.com
Assignment via
[Control
/Bkr
/Pos Indicatrs Wirng]
[Control
/Bkr
/Pos Indicatrs Wirng]
[Control
/Bkr
/Pos Indicatrs Wirng]
[Control
/Bkr
/Synchron Switchg]
[Control
/Bkr
/Trip Manager]
[Control
/Bkr
/Interlockings]
[Control
/Bkr
/Interlockings]
[Control
/Bkr
/Interlockings]
[Control
/Bkr
/Interlockings]
[Control
/Bkr
/Interlockings]
[Control
/Bkr
/Interlockings]
IM02602003E