Voltage Supply
Aux. Voltage:
Buffer Time in Case of Supply Failure:
Max. Permissible Making Current:
The voltage supply must be protected by a fuse of:
2,5 A time-lag miniature fuse 5 x 20 mm (approx. 1/5 x 0.8 in.) according to IEC 60127
3,5 A time-lag miniature fuse 6,3 x 32 mm (approx. 1/4 x 1 ¼ in.) according to UL 248-14
Power Consumption
Power Supply Range:
24 - 270 Vdc:
48 - 230 Vac
(For Frequencies of 50-60 Hz):
EDR-3000
24 - 270 Vdc / 48 - 230 Vac (-20/+10%)
>= 50 ms at minimal aux. voltage
Interrupted communication is permitted.
18 A peak value for <0.25 ms
12 A peak value for <1 ms
Power consumption
in Idle Mode
Approx. 7 W
Approx. 7 W / 13 VA
www.eaton.com
≂
Max. Power Consumption
Approx. 10 W
Approx. 10W /17 VA
IM02602003E