Error Messages / Codes
After a reboot of the device, the reason for rebooting will be displayed under [Operation/Status Display/Sys/Reboot].
For more information about the reboot reason, please refer to the information in this section.
The reboot will also be logged within the event recorder. Rebooting causes an event named "Sys.Reboot".
Numeric Reboot Codes
1.
Reboot after clean switching off of the device - Normal reboot after clean shut-down of the device.
2.
Reboot by User command - User-initiated reboot through panel command.
3.
Super reset - Reset to factory settings.
4.
Restart by debugger - Eaton internally for system-analysis purposes.
5.
Restart because of configuration changes.
6.
General failure - Reboot without definite reason.
7.
Reboot by "SW-system abort" (HOST-side) - Summary of several reboot reasons detected by the
software (i.e.: wrong pointer, corrupted files, etc.).
8.
Reboot by watchdog timeout (HOST-side) - Signaling if the protection-class-task hangs.
9.
Reboot by system abort (DSP-side) - Summary of several reboot reasons detected by software (i.e.:
wrong pointer, DSP-side).
10.
Reboot by watchdog timeout (DSP-side) - Appears when DSP sequence needs too long for one cycle.
11.
Loss of auxiliary voltage or low voltage reboot after loss of auxiliary voltage or voltage dropping below
reboot level but not becoming zero.
12.
Faulty memory access - Message of MMU (memory mapping unit) that prohibited memory access has
occurred.
EDR-3000
Error Messages/Codes
www.eaton.com
IM02602003E
586