Technical Data of the 230 V Class

2.2
Technical data of the 230 V class
Inverter size
Housing size
Phases
Output rated power
Max. rated motor power
Output rated current
Max. short time current
OC-tripping current
Input rated current
Max. permissible main fuse gG
Rated switching frequency
Max. switching frequency
Power loss at nominal operating
Power loss at DC operating
Standstill current at 4 kHz
Standstill current at 8 kHz
Standstill current at 16 kHz
Min. frequency at continuous full load
Max. heat sink temperature
Motor cable cross-section
Min. braking resistor
Max. braking current
Overload characteristic (see annex)
Input rated voltage
Input voltage range (Uin)
Input voltage at DC operation
Mains frequency
Output voltage
Output frequency
Max. motor line length shielded at 4 kHz
Max. motor line length shielded at 8 kHz
Max. motor line length shielded at 16 kHz
For use in USA
Max. mains fuse type RK5
MCCB: NKJH Type „E"
1) With the regulated systems F5-M as well as F5-S 5% are to be subtracted as control reserve
2) Max. current before response of the OL-function (F5-M, F5-S, F5-A)
3) Recommended minimum cross section of the motor line for rated power and a cable length of upto 100 m (copper)
4) This data is only valid for units with internal brake transistor GTR 7 (see "unit identification")
5) At units with integrated filter (see „unit identification"):
up to max. 5 m (10 m at housing A) line length and 4 kHz switching frequency = Limit value B (EN 55011)
up to max. 10 m line length and 16kHz switching frequency = Limit value A (EN 55022)
6) For UL accepted types see annex
The technical data are for 2- / 4-pole standard motors. With other pole numbers the inverter must be dimensioned onto the
motor rated current. Contact KEB for special or medium frequency motors.
Site altitude maximal 2000 m. With site altitudes over 1000 m a derating of 1 % per 100 m must be taken into con-
sideration.
05
A
B
1
1
3
[kVA]
0.9
[kW]
0.37
[A]
2.3
1)
[A]
4.1
[A]
5.0
[A]
4.6
4.6 3.2
[A]
16
16
[kHz] 4
16
[kHz] 8
16
[W]
30
50
60
[W]
28
48
55
2)
[A]
2.3
2)
[A]
2.3
2)
[A]
2.3
[Hz]
[°C]
100
90
95
3)
1.5
1.5
[mm²]
4)
56
[Ω]
100
100
4)
[A]
4.5
7.5
4.5
[V]
[V]
[V]
[Hz]
[V]
[Hz]
5) [m]
10
30
10
5) [m]
10
20
10
5) [m]
10
[A]
10 10
6
15
6)
[A]
10 10 6.3
16
07
A
B
D
1
1
3
1
3
1
1.6
0.75
4
7.2
8.6
8
8
5.6
8
5.6
14
20 16 20 16 20 16 20 16 25 20 25 20
8
16
8
16
65
100
90
60
90
80
4
4
4
6
90
2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5
56
56
7.5
7.5
1
230 (UL: 240)
180...260 ±0
250...370 ±0
50 / 60 ±2
3 x 0...Uin
see control board
100
100
100
50
50
100
20
20
40
15 10 15 10 20 15 20 15 30 25 30 25
16 10 16 10 20 16 16 20 25 20 25 20
09
10
B
D
B
D
3
1
3
1
3
1
2.8
4.0
1.5
2.2
7
10
12.6
18
15.1
21.6
9.8
14
9.8
20 14 20 14
16
8
16
16
16
130
105
170
120
90
155
7
10
7
10
7
8.5
10
90
90
4 2.5 4 2.5
47
33
9.5
12
100
100
100
100
100
100
GB - 15