Technical Data of the 400 V Class

2.3
Technical Data of the 400 V Class
Inverter size
Housing size
Phases
Output rated power
Max. rated motor power
Output rated current
Max. short time current
OC-tripping current
Input rated current
Max. permissible main fuse gG
Rated switching frequency
Max. switching frequency
Power loss at nominal operating
Power loss at DC supply
Standstill current at 4 kHz
Standstill current at 8 kHz
Standstill current at 16 kHz
Min. frequency at continuous full load
Max. heat sink temperature
Motor cable cross-section
Min. braking resistor
Max. braking current
Overload characteristic
Input rated voltage
Input voltage range
Input voltage at DC operation
Mains frequency
permitted mains forms
Output voltage
Output frequency
Max. motor line length shielded
Cooling mode (L=air; W=water)
Cooling water content
1)
With the regulated operating modes MULTI and SERVO 5 % are to be subtracted as control reserve
2)
Max. current before the OL2 function triggers (in operating mode MULTI and SERVO)
3)
Recommended minimum cross section of the motor line for rated power and a cable length of upto 100 m (CU)
4)
This data is only valid for units with internal brake transistor GTR 7 (see "unit identification")
5)
At rated voltages > 460 V multiply the rated current with factor 0.86
6)
At control board BASIC only 2 kHz, with COMPACT 8 kHz
7)
Protection in accordance with UL see annex B
8)
Restrictions when using HF filter
9)
Phase conductor grounded mains are only permissible without HF filters
10) The voltage at the motor is dependent on the series-connected units and on the control method (see A.3)
11) The output frequency is to be limited in such way that 1/10 of the switching frequency is not exceeded
The technical data are for 2-/4-pole standard motors. With other pole numbers the inverter
must be dimensioned onto the motor rated current. Contact KEB for special or medium fre-
quency motors.
GB - 14
15
16
H
H
3
3
[kVA] 17
23
[kW] 11
15
[A] 24
33
[A] 36
49.5
1)
[A] 43
59
[A] 31
43
[A] 35
50
7)
[kHz] 16
16
[kHz] 16
16
[W] 360
490
[W] 320
430
[A] 24
33
2)
[A] 24
33
2)
[A] 24
33
2)
[Hz]
3
3
[mm²]
6
10
3)
[Ω] 22
22
4)
[A] 37
37
4)
[V]
5)
[V]
[V]
[Hz]
TN, TT, IT
[V]
10)
[Hz]
11)
[m]
L W L W L W L W L W L W
17
18
19
H
H
H
3
3
3
29
35
42
18,5
22
30
42
50
60
63
75
90
75
90
108
55
65
66
63
80
80
8
8
4
16
16
16
470
610
540
400
525
425
42
50
60
42
50
54
25
30
36
3
3
3
90 °C (194 °F)
16
25
25
22
13
13
37
63
63
(see annex A)
400 (UL: 480)
305...528 ±0
420...746 ±0
50 / 60 ±2
, ∆ mains
8)
9)
3 x 0...Uin
see control board
100
350 ml
20
H
3
52
37
75
112
135
83
100
2
8
640
500
67.5
52.5
3
35
9
88
50