Ip Address For Siwarex; Entering A Known Siwarex Ip Address; Determining An Unknown Ip Address; Setting Up A Network - Siemens SIWAREX WP241 Manual

Electronic weighing system
Table of Contents

Advertisement

7.6.3

IP address for SIWAREX

The factory-set IP address is 192.168.0.21. This address is also preset in SIWATOOL. The
connection to a SIWAREX module can be established immediately. The network card used
must be configured for this network.
If the connection is to be established to a specific SIWAREX module, its IP address must be
set in SIWATOOL. The setting is carried out with the menu item "Communication/Set
Ethernet Configuration...".
If the IP address of a SIWAREX module is unknown, it can be determined using the
additional program "Primary Setup Tool". The program is included in the SIWAREX
configuration package.
During the setup, a new IP address can be assigned to the module using SIWATOOL.
The assignment of a new IP address to a SIWAREX module is necessary if several
SIWAREX modules are present in one network.
The following ports are used by SIWAREX:
● SIWATOOL port: 23006
● MODBUS TCP/IP port: 502
● TFTP for firmware download port: 69
7.6.3.1

Entering a known SIWAREX IP address

To establish a connection to a SIWAREX module, enter the IP address in SIWATOOL.
Under the menu item "Communication", select "Set Ethernet Configuration...". Enter the IP
address of the SIWAREX module in the following window. To activate the IP address and
establish a connection to the SIWAREX module, subsequently click on "Online".
7.6.3.2

Determining an unknown IP address

If the IP address of a connected SIWAREX module is unknown, it can be determined using
the program "Primary Setup Tool". The program is included in the configuration package.
Install the program "Primary Setup Tool". When started, the program can determine the
Siemens devices present in the network.
The MAC (Media Access Control) address can be read on the front of the SIWAREX
module. Every device has an MAC address which is unique worldwide.
The IP address can be determined from the identified MAC address. The Primary Setup Tool
also allows the IP address of a SIWAREX module to be set/changed.
Additional information on the Primary Setup Tool can be found in the associated manual.
7.6.3.3

Setting up a network

Several SIWAREX modules can be connected together in a network via a switch. Via the
network, you can use SIWATOOL to assign parameters to and start the various modules or
connect a common Operator Panel.
SIWAREX WP241
Manual, 04/2014, A5E33713528A
Commissioning
7.6 Service with SIWATOOL software
63