Set Instrument Address - Siemens SITRANS LG270 Operating Instructions Manual

Profibus pa rod and cable probe
Table of Contents

Advertisement

Electronics compartment
Connection compartment
Instrument address
PBD-51041506
Fig. 16: Electronics compartment - double chamber housing
1
Internal connection to the connection compartment
2
Contact pins for the display and adjustment module or interface adapter
3
Selection switch for bus address
1
Fig. 17: Connection compartment - double chamber housing
1
Voltage supply, signal output
2
For display and adjustment module or interface adapter
3
For external display and adjustment unit
4
Ground terminal for connection of the cable screening
5.5

Set instrument address

An address must be assigned to each Profibus PA instrument. The
approved addresses are between 0 and 126. Each address must
only be assigned once in the Profibus PA network. The sensor is only
recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is set. This address can
be used to test the function of the instrument and to connect it to a
Profibus PA network. Then the address must be changed to integrate
additional instruments.
The address setting is carried out either via:
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
The display and adjustment module (address setting via software)
PACTware/DTM (address setting via software)
SITRANS LG270 - Operating Instructions
0
0
0
Bus
+
1
2
5
6 7 8
( )
(-)
1
1
Bus
+
1
2
5
6 7 8
( )
(-)
2
3
2
3
4
27