Lod Boost Level; Lod Boost Time/Lod Delay Time; Lod Feedback Level; Lod Input Selection - Toshiba Q7 Installation And Operation Manual

Table of Contents

Advertisement

LOD Boost Level

LOD Boost Level
Program
PID Setup
The Low Output Disable feature adds the user-input frequency value to the
commanded frequency (Hz).
LOD Boost Time
Program
PID Setup
The Low Output Disable Boost Time sets the on-time timer for the LOD
Boost function.
Once expired, the LOD Boost function ceases.
LOD Delay Time
Program
PID Setup
The Low Output Disable Delay Time sets the amount of time that the LOD
Start Level criteria must be met and maintained for the LOD function to be
initiated.

LOD Feedback Level

Program
PID Setup
The Low Output Disable Feedback Level sets a frequency level that, until the
output of the ASD drops below this setting, the Restart Delay Timer does not
start.

LOD Input Selection

Program
PID Setup
Enables/Disables the LOD function and, if enabled, selects a stopping method.
Settings:
Disabled
Enabled — Decel Stop
Enabled — Coast Stop
Q7 ASD Installation and Operation Manual
LOD Boost Level
LOD Boost Time
LOD Delay Time
LOD Feedback Lvl
LOD Input Sel
LOD Input Selection
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
73