Rs485 Master Output; Rs485 Response Time; Rs485 Wire Count; Run Frequency - Toshiba Q7 Installation And Operation Manual

Table of Contents

Advertisement

RS485 Master Output

RS485 Master Output
Program
Comm Settings
In a master/follower configuration, this setting determines the output parameter
of the master ASD that will be used to control the applicable follower ASDs.
Note: Select Normal if TTL Master Out is configured as a Master
Output controller. Otherwise, a keypad failure will result.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
Normal (No Slave)
Frequency Reference
Output Command Frequency
Torque Command
Output Torque

RS485 Response Time

Program
Comm Settings
This parameter sets the RS232/485 response delay time.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

RS485 Wire Count

Program
Comm Settings
This parameter sets the communications protocol to the 2 or 4 wire method.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
2 wire
4 wire

Run Frequency

Program
Special Controls
This parameter establishes a center frequency (Run Frequency) of a frequency
band.
The Run Frequency Hysteresis parameter provides a plus-or-minus value for
the Run Frequency; thus, establishing a frequency band.
During acceleration, the ASD will not output a signal to the motor until the
lower level of the band is reached.
During deceleration, the ASD will continue to output the programmed
deceleration output signal to the motor until the lower level of the band is
reached; at which time the output will go to 0.0 Hz.
104
RS485 Master Out
RS485 Res Time
RS485 Wire Count
Run Frequency
Run Frequency
Parameter Type — Selection List
Factory Default — Normal (No Slave)
Changeable During Run — Yes
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
Parameter Type — Selection List
Factory Default — 4-Wire
Changeable During Run — Yes
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Q7 ASD Installation and Operation Manual