RES Terminal
RES Terminal
Program
Input Terminals
This parameter selects the functionality of the RES discrete input terminal.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable RES terminal to 1 of the 69 possible
functions that are listed in
RES Terminal Delay
Program
Terminal Delays
This parameter delays the response of the ASD to any change in the RES
terminal input by the programmed value (see waveforms at
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Ridethrough Mode

Program
Protection
Enables/Disables the Ridethrough function.
In the event of a momentary power outage, when enabled, the Ridethrough
function uses regenerative energy to maintain the control circuitry settings.
Regenerated energy is not used to drive the motor.

Ridethrough Time

Program
Protection
This parameter determines the length of the Ridethrough time. The
Ridethrough will be maintained for the number of seconds set using this
parameter.
Note: The actual Ridethrough Time is load-dependent.

R Terminal

Program
Input Terminals
This parameter selects the functionality of the R discrete input terminal.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable R terminal to 1 of the 69 possible
functions that are listed in
Q7 ASD Installation and Operation Manual
RES Terminal
Table 7 on page
130.
RES Delay
Ridethrough Mode
Ridethrough
R Terminal
Table 7 on page
130.
Parameter Type — Selection List
Factory Default — Reset
Changeable During Run — No
Parameter Type — Numerical
Factory Default — 8.0
F Terminal
Delay).
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Parameter Type — Numerical
Factory Default — 2.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 320.0
Units — Seconds
Parameter Type — Selection List
Factory Default — Reverse
Changeable During Run — No
R Terminal
99