Overvoltage Stall Level (2)
Overvoltage Stall Level (2)
Program
Protection
This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an Overvoltage Stall. An Overvoltage Stall increases the output
frequency of the ASD during deceleration for a specified time in an attempt to
prevent an Overvoltage Trip.
If the overvoltage condition persists for over 4 mS, an Overvoltage Trip will
be incurred.
Note: This feature may increase deceleration times.

Overvoltage Stall Level (fast)

Program
Protection
This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an Overvoltage Stall. An Overvoltage Stall increases the output
frequency of the ASD during deceleration for a specified time in an attempt to
prevent an Overvoltage Trip.
If the overvoltage condition persists for over 250 µS, an Overvoltage Trip will
be incurred.
Note: This feature may increase deceleration times.

Panel Acc/Dec Select

Program
Panel Control
This parameter is used to select 1 of 4 accel/decel profiles that may be
configured and run. Each accel/decel profile is comprised of 3 user settings:
Acceleration, Deceleration, and Pattern.
Panel Direction
Program
Panel Control
This parameter sets the motor direction while operating from the keypad.
Panel Lockout
Program
Utility Group
This parameter disables the selected keypad function.
Settings:
Allow All Keys
Allow Emergency Off Only

Panel PID Control

Program
Panel Control
Enables/Disables PID control while operating from the keypad.
Q7 ASD Installation and Operation Manual
OvrVolt Level 2
OvrVolt Level 1
Pnl Acc/Dec Sel
Panel Direction
Panel Lockout
Panel PID Ctrl
Panel PID Control
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 50.0
Maximum — 250.0
Units — %
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 50.00
Maximum — 250.0
Units — %
Parameter Type — Selection List
Factory Default — Accel/Decel #1
Changeable During Run — Yes
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — Yes
Parameter Type — Selection List
Factory Default — Allow All Keys
Changeable During Run — Yes
Parameter Type — Selection List
Factory Default — Enabled