PG Speed Frequency #2
PG Speed Frequency #2
Program
Freq Settings
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
This parameter sets
PG Speed Frequency #2
associated with the

PG Speed Reference #2

See
PG Speed Frequency #1
PG Speed Reference #1
Program
Freq Settings
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
This parameter sets the PG input pulse count that represents
Frequency #1
(direction/speed) and is entered as a percentage of the full ±
range.
The range of values for this parameter is -100 to +100% of the PG input pulse
count range.
See
PG Speed Frequency #1
PG Speed Reference #2
Program
Freq Settings
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
This parameter sets the PG input pulse count that represents
Frequency #2
(direction/speed) and is entered as a percentage of the full ±
range.
See
PG Speed Frequency #1

Power Switching

Program
Special Controls
This parameter Enables/Disables the Powerline Switching feature. When
enabled, the system is instructed to discontinue using the output of the drive and
to switch to the commercial power in the event of a trip or when reaching a
user-set frequency.
This feature may also be activated via a discrete input terminal (see
page 130
for further information on this feature).
Settings:
Disabled
On Trip
At Frequency
Trip or At Frequency
88
PG Speed Freq #2
and is the frequency that is
setting.
for further information on this setting.
PG Speed Ref #1
for further information on this setting.
PG Speed Freq #2
for further information on this setting.
Power Switching
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
PG Speed
Minimum — -100.0
Maximum — +100.0
Units — %
Parameter Type — Numerical
Factory Default — +100.00
Changeable During Run — Yes
PG Speed
Minimum — -100.0
Maximum — +100.0
Units — %
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Table 7 on
Q7 ASD Installation and Operation Manual
Power Switching