RX Speed Frequency #2

RX Speed Frequency #2
Program
Freq Settings
This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Speed Control mode.
See
RX Speed Frequency #1
This parameter sets
RX Speed Frequency #2
associated with the setting of
Speed Control mode.

RX Speed Reference #1

Program
Freq Settings
This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Speed Control or the Torque Control mode.
See
RX Speed Frequency #1
for Speed control.
See
RX Torque Reference #1
for Torque control.
This parameter sets the RX input level that is associated with
Frequency #1
when operating in the Speed control mode or is associated with
the
RX Torque Reference #1
This value is entered as -100 to +100% of the -10 to +10 VDC RX input signal
range.

RX Speed Reference #2

Program
Freq Settings
This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Speed Control or the Torque Control mode.
See
RX Speed Frequency #1
for Speed control.
See
RX Torque Reference #1
for Torque control.
This parameter sets the RX input level that is associated with
Frequency #2
when operating in the Speed control mode or is associated with
the
RX Torque Reference #2
This value is entered as -100 to +100% of the -10 to +10 VDC RX input signal
range.
106
RX Speed Freq #2
for further information on this setting.
and is the frequency that is
RX Speed Reference #2
when operating in the
RX Speed Ref #1
for further information on this setting when used
for further information on this setting when used
when operating in the Torque control mode.
RX Speed Ref #2
for further information on this setting when used
for further information on this setting when used
when operating in the Torque control mode.
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — -Max. Freq.
Maximum — +Max. Freq.
Units — Hz
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.0
Maximum — 100.0
Units — %
RX Speed
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — -100.0
Maximum — 100.0
Units — %
RX Speed
Q7 ASD Installation and Operation Manual
RX Speed Reference #2