FM Terminal Assignment

FM Terminal Assignment
Program
Meter Terminal Adjustment Parameters
This setting determines the output function of the FM analog output terminal.
The FM output terminal produces an output current that is proportional to the
magnitude of the function assigned to this terminal. The available assignments
for this output terminal are listed in
The FM analog output has a maximum resolution of 1/1024. SW-2 may be
switched to allow for the full-range output to be either 0 – 1 mA or 4 – 20 mA
when providing an output current, or either 0 – 1 or 1 – 7.5 volts when
providing an output voltage at this terminal.

FP Terminal Adjustment

Program
Output Terminals
This parameter sets the full-scale reading of the FP terminal. The full-scale
reading of the monitored variable selected in FP Terminal Setting may be set
here.

FP Terminal Setting

Program
Output Terminals
This parameter commands the multifunction programmable FP terminal to
monitor the value of 1 of 31 possible system functions. As the monitored
function changes in magnitude or frequency, the pulse count of the FP output
pulse train changes in direct proportion to changes in the monitored function.
As the monitored value goes up so does the pulse count of the FP output.
Note: The duty cycle of the output pulse train remains at
65 ±5.0 µS.
Possible assignments for this output terminal are listed in

Frequency Command Panel

Program
PID Setup
While operating using PID control, this parameter sets the reference frequency.
66
Table 6 on page
48.
FP Terminal Adj
FP Terminal Set
Freq Cmd Pnl
FM
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Parameter Type — Numerical
Factory Default — 3.840
Changeable During Run — Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Table 6 on page
48.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Q7 ASD Installation and Operation Manual
Frequency Command Panel