On Terminal; Out1 Off Delay; Out1 On Delay; Out1 Terminal - Toshiba Q7 Installation And Operation Manual

Table of Contents

Advertisement

ON Terminal

ON Terminal
Program
Input Terminals
This parameter selects the functionality of the ON discrete input virtual
terminal.
As a virtual terminal, the ON control terminal exists only in memory and is
considered to always be in its True (or connected to CC) state.
It is often practical to assign this terminal to a function that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable ON terminal to 1 of the 69 possible
functions that are listed in
In addition, the input terminal must be specified as Normally Open or
Normally Closed.

OUT1 Off Delay

Program
Terminal Delays
Once the condition is met to change the state of the OUT1 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at
FL Off
The on and off delay times of the OUT1 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.

OUT1 On Delay

Program
Terminal Delays
Once the condition is met to change the state of the OUT1 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at
FL On
The delay may be increased to prevent relay chatter.

OUT1 Terminal

Program
Output Terminals
This parameter sets the functionality of the OUT1 (A & C) output contacts to 1
of the 58 possible functions that are listed in
The on and off delay times of the OUT1 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output contacts must be specified as Normally Open or
Normally Closed.
Q7 ASD Installation and Operation Manual
On Terminal
Table 7 on page
130.
OUT1 Off Delay
Delay).
OUT1 On Delay
Delay).
OUT1 Terminal
Table 8 on page
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Parameter Type — Selection List
Factory Default — Damper Cmd
133.
Changeable During Run — No
OUT1 Terminal