Bin Torque Reference #1; Bin Input Torque Control Setup; Torque Control; Bin Torque Reference #2 - Toshiba Q7 Installation And Operation Manual

Table of Contents

Advertisement

BIN Torque Reference #1

BIN Torque Reference #1
Program
Freq Settings
This parameter is used to set the direction, gain, and bias of the discrete input
terminals when using the discrete input terminals as the control input while
operating in the Torque Control mode.

BIN Input Torque Control Setup

Perform the following setup to allow the system to receive Torque control input
from the discrete input terminals:
Program
Utility Group
Program
Utility Group
Program
Input Terminals; select and set the desired discrete input
terminals to Bin Bit(s) 0 – 7 or 0 – MSB (see
listing of the available terminal settings). The binary terminal input word
will control the direction, speed, and torque of the motor.
Provide a Run command (F or R).

Torque Control

When operating in the Torque Control mode, scaling of the discrete input
terminals is accomplished via the following parameters as described below:
BIN Torque Reference 1,
the binary input value (% of 255
Torque Reference 1,
BIN Torque Reference 2, and
the binary input value (% of 255
Torque Reference 2.
This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input.
This parameter sets BIN Torque Reference 1 and is the output torque value
that is associated with the setting of BIN Speed Reference 1 when operating in
the Torque control mode.
This value is entered as -250% to 250% of the output torque range.

BIN Torque Reference #2

Program
Freq Settings
This parameter is used to set the direction, gain, and bias of the discrete input
terminals when using the discrete input terminals as the control input while
operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input.
See
BIN Torque Reference #1
This parameter sets BIN Torque Reference 2 and is the output torque value
that is associated with the setting of BIN Speed Reference 2 when operating in
the Torque control mode.
This value is entered as -250% to 250% of the output torque range.
Q7 ASD Installation and Operation Manual
BIN Torque Ref 1
Command Mode
Terminal Block.
Frequency Mode
Use Binary/BCD Input.
Table 7 on page 130
) (BIN Speed Ref #1) that represents BIN
D
) (BIN Speed Ref #2) that represents BIN
D
BIN Torque Ref 2
for further information on this setting.
BIN Torque Reference #2
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
for a
Torque Settings
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
53