VI/II Speed Reference #1

VI/II Speed Reference #1
Program
Freq Settings
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
See
VI/II Speed Frequency #1
used for Speed control.
See
VI/II Torque Reference #1
used for Torque control.
This parameter sets the VI/II input level that is associated with
Frequency #1
when operating in the Speed control mode or is associated with
the
VI/II Torque Reference #1
This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal
range.
The default value for this parameter is 20%. The II input is commonly used for
the 4 – 20 mA current loop signal where 4 mA equals 20% of a 20 mA signal.
If the VI input is used (0 – 10 VDC input), this parameter may be changed to
0.0% (of the input signal).
VI/II Speed Reference #2
Program
Freq Settings
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
See
VI/II Speed Frequency #1
used for Speed control.
See
VI/II Torque Reference #1
used for Torque control.
This parameter sets the VI/II input level that is associated with
Frequency #2
when operating in the Speed control mode or is associated with
the
VI/II Torque Reference #2
This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal
range.
Q7 ASD Installation and Operation Manual
VI/II Spd Ref #1
for further information on this setting when
for further information on this setting when
when operating in the Torque control mode.
VI/II Spd Ref #2
for further information on this setting when
for further information on this setting when
when operating in the Torque control mode.
Parameter Type — Numerical
Factory Default — 20.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Speed
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Speed
VI/II Speed Reference #2
127