Type Reset
Reset
Type Reset
Program
Utility Group
This feature assists the user when performing fault analysis or by allowing a
quick system setup change when required. Performing a Type Reset results in
one of the following user-selected post-reset configurations.
Settings:
Auto Setup for 50 Hz
Auto Setup for 60 Hz
Restore Factory Defaults
Clear Past Trips
Clear Run Timer
Typeform (New Base Drive Board)
Save User Parameters
Restore User Parameters
Undervoltage Stall Level
Program
Protection
This parameter sets the low end of the DC bus voltage threshold that, once it
drops below this setting, will activate the Ridethrough feature, if enabled.
Activation may be the result of a momentary power loss or an excessive load on
the bus voltage. Once activated, the system will attempt to maintain the bus
voltage level set here until the motor stops.
Note: This feature may decrease deceleration times.
Undervoltage Time
Program
Protection
This parameter sets the time that the undervoltage condition must exist to cause
an Undervoltage Trip when this function is enabled at the Undervoltage Trip
parameter.
Undervoltage Trip
Program
Protection
This parameter Enables/Disables the Undervoltage Trip function.
With this parameter Enabled, the ASD will trip if the undervoltage condition
persists for a time greater than the Undervoltage Time setting.
A user-selected contact may be actuated if so configured.
If Disabled the ASD will stop and not trip; the FL contact is not active.
124
Type Reset
UV Stall Level
Undervoltage/Ridethrough
Undervolt Trip
Undervoltage Trip
Parameter Type — Selection List
Factory Default — No Reset
Changeable During Run — No
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 50.00
Maximum — 100.0
Units — %
Parameter Type — Numerical
Factory Default — 0.03
Changeable During Run — No
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Q7 ASD Installation and Operation Manual