Event Records - GE b30 Instruction Manual

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

RECORDS
This menu displays the user-programmable fault report actual values. See the User-Programmable Fault Report section in
chapter 5 for information on this feature.

6.5.2 Event records

ACTUAL VALUES  RECORDS  EVENT RECORDS
 EVENT RECORDS
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. See the
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log
operating phase output only without asserting the common three-phase operand event.
See also the system log (syslog) information in the previous chapter.
The event records are also viewable in the software and in a web browser. The figure shows the event records in the
software. To view them in a web browser, enter the IP address of the device.
6
6-22
EVENT: XXX
XXX
EVENT: 3
POWER ON
EVENT: 2
POWER OFF
EVENT: 1
EVENTS CLEARED
COMMANDS
 CLEAR RECORDS
Figure 6-5: Event records viewed in EnerVista software
Date and time stamps
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
menu for clearing event records.
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES

Advertisement

Table of Contents
loading

Table of Contents