Application Of Settings; Overview; Introduction - GE b30 Instruction Manual

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

B30 Bus Differential System
Chapter 8: Application of settings

Application of settings

This chapter provides example(s) of use.

8.1 Overview

8.1.1 Introduction

The B30 is a high-speed low-impedance microprocessor-based current differential relay for power system busbars. The
relay is limited to six circuits. The B30 incorporates the dynamic bus replica mechanism that allows for protecting buses
with circuits interconnectable between various sections but with single current measurement points.
The relay uses a dual-slope dual-breakpoint differential characteristic with the restraint signal created as the maximum
among the magnitudes of the circuit connected to the protected bus. The low-impedance operating principle is enhanced
by the use of the Saturation Detector and a current directional principle.
This chapter provides an example of setting calculations for a sample bus. The selected example includes various bus
configurations to clarify a number of typical situations. Both the bus configuration and numerical data used are not meant
to reflect any specific utility practice or design standards.
It is also assumed that the CTs have been selected without considering a B30 application, but the UR settings are to be
calculated for proper relay application. The CT data used in this example are kept to a minimum and in a generic form. The
CT data does not reflect any particular notation or national standards.
The analysis provided in this chapter has been performed with the following goals:
The limits of linear operation of the CTs considering zero remanent flux have been determined in order to select the
high breakpoint settings of the biased differential characteristic
The limits of linear operation of the CTs considering a remanent flux of 80% have been determined in order to select
the low breakpoint settings of the biased differential characteristic
Saturation of the CTs has been analyzed in order to select the higher slope of the biased differential characteristic and
the high set differential overcurrent setting
The analysis tools and safety margins applied are examples only and do not reflect any particular protection philosophy.
Typically, for the CT saturation related calculations, it is sufficient to consider the weakest (most prone to saturation) CT
connected to the bus and the total bus fault current combined with the longest time constant among all the circuits
connected to the bus. This chapter provides more detailed analysis (see the Slopes and High Set Threshold section) in order
to illustrate the idea of using setting groups to enhance the B30 performance when the bus configuration changes (see
the Enhancing Relay Performance section).
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
8-1

Advertisement

Table of Contents
loading

Table of Contents