GROUPED ELEMENTS
5
5.7.4.4 Phase instantaneous overcurrent (ANSI 50P, IEC PIOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE IOC 1(12)
 PHASE IOC 1
5-180
Figure 5-88: Phase time overcurrent 1 logic
PHASE IOC1
FUNCTION: Disabled
PHASE IOC1 SIGNAL
SOURCE: SRC 1
PHASE IOC1
PICKUP: 1.000 pu
PHASE IOC1 PICKUP
DELAY: 0.00 s
PHASE IOC1 RESET
DELAY: 0.00 s
PHASE IOC1 BLOCK A:
Off
PHASE IOC1 BLOCK C:
Off
PHASE IOC1
TARGET: Self-reset
PHASE IOC1
EVENTS: Disabled
CHAPTER 5: SETTINGS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.020 to 30.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL