PRODUCT SETUP
3.
Change the default password of ChangeMe1# as outlined in the Set Up CyberSentry and Change Default Password
section at the end of the Installation chapter.
Password requirements
A user account requires an alpha-numeric password that meets the following requirements:
Password is case-sensitive
Password cannot contain the user account name or parts of the user account that exceed two consecutive
characters
Password must be at least eight characters in length
Password must contain characters from all of the following categories:
English uppercase characters (A through Z)
English lowercase characters (a through z)
Base 10 digits (0 through 9)
Non-alphabetic characters (for example, ~, !, @, #, $,%, &)
5.3.1.2 Password security
SETTINGS  PRODUCT SETUP  SECURITY
 SECURITY
5
The B30 supports password entry from a local or remote connection.
Local access is defined as access to settings or commands via the faceplate. This includes both keypad entry and the
RS232 port. Remote access is defined as access to settings or commands via any rear communications port. This includes
both Ethernet and RS485 connections. Any change to the local or remote password enables this functionality.
— The "Restricted" option means that settings and commands can be accessed, but there is no access to
ACCESS LEVEL
factory configuration. Access automatically reverts to the Restricted level according to the access level timeout setting
values. The access level is set to Restricted when control power is cycled.
The "Factory Service" level is not available and intended for factory use only.
There are two user security access levels, setting and command, for which you can set a password for each. Use of a
password for each level controls whether users can enter commands or change settings. Another option is to specify
setting and/or command access for individual user accounts.
Setting — Allows the user to make any changes to any of the setting values:
Changing any setting
Test mode operation
Command — Restricts the user from making any settings changes, but allows the user to perform the following
operations:
Changing the state of virtual inputs
Clearing the event records
5-8
ACCESS LEVEL:
Restricted
 CHANGE LOCAL
 PASSWORDS
 CHANGE REMOTE
 PASSWORDS
 ACCESS
 SUPERVISION
 DUAL PERMISSION
 SECURITY ACCESS
PASSWORD ACCESS
EVENTS: Disabled
CHAPTER 5: SETTINGS
Range: Restricted, Command, Setting,
Factory Service (for factory use only)
See page 5-9
See page 5-10
See page 5-10
See page 5-11
Range: Disabled, Enabled
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL