CHAPTER 5: SETTINGS
Operand type
Operand syntax
ELEMENT:
THERMAL PROT 1 PKP
Thermal overload
THERMAL PROT 1 OP
protection
THERMAL PROT 2
ELEMENT:
TRIP BUS 1 PKP
Trip bus
TRIP BUS 1 OP
TRIP BUS 2 to 6
FIXED OPERANDS
Off
On
INPUTS/OUTPUTS:
Cont Ip 1 On
Contact inputs
Cont Ip 2 On
↓
Cont Ip 1 Off
Cont Ip 2 Off
↓
Cont Ip 96 On
Cont Ip 96 Off
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
↓
current
(from detector on
Cont Op 64
form-A output only)
INPUTS/OUTPUTS:
Cont Op 1 VOn
Contact outputs,
Cont Op 2
voltage
↓
(from detector on
Cont Op 64
form-A output only)
Cont Op 1
Cont Op 2
↓
Cont Op 64
INPUTS/OUTPUTS:
DIRECT INPUT 1 On
Direct inputs
↓
DIRECT INPUT 32 On
INPUTS/OUTPUTS:
RxG DPS 1 BAD
RxGOOSE DPS
RxG DPS 1 INTERM
RxG DPS 1 OFF
RxG DPS 1 ON
RxG DPS 2 to 5
INPUTS/OUTPUTS:
RxG Bool 1 On
RxGOOSE Booleans
RxG Bool 2 On
RxG Bool 3 On
↓
RxG Bool 32 On
INPUTS/OUTPUTS:
Virt Ip 1 On
Virtual inputs
Virt Ip 2 On
Virt Ip 3 On
↓
Virt Ip 64 On
INPUTS/OUTPUTS:
Virt Op 1
Virtual outputs
Virt Op 2
Virt Op 3
↓
Virt Op 96
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Operand description
Thermal overload protection 1 picked up
Thermal overload protection 1 operated
Same set of operands as shown for THERMAL PROT 1
Asserted when the trip bus 1 element picks up
Asserted when the trip bus 1 element operates
Same set of operands as shown for TRIP BUS 1
Logic = 0. Does nothing and can be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
IOn
(does not appear unless ordered)
IOn
(does not appear unless ordered)
↓
IOn
(does not appear unless ordered)
(does not appear unless ordered)
VOn
(does not appear unless ordered)
↓
VOn
(does not appear unless ordered)
VOff
(does not appear unless ordered)
VOff
(does not appear unless ordered)
↓
VOff
(does not appear unless ordered)
Flag is set, logic=1
↓
Flag is set, logic=1
Asserted while the RxGOOSE double-point status input is in the bad state
Asserted while the RxGOOSE double-point status input is in the intermediate
state
Asserted while the RxGOOSE double-point status input is off
Asserted while the RxGOOSE double-point status input is on
Same set of operands as per RxG DPS 1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
↓
On
Flag is set, logic=1
FLEXLOGIC
5
5-153