GE b30 Instruction Manual page 336

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

GROUPED ELEMENTS
CHAPTER 5: SETTINGS
in their linear mode, i.e. in load conditions and during distant external faults. When adjusting this setting, it must be kept in
mind that the restraining signal used by the biased bus differential protection element is created as the maximum of all the
input currents.
— This setting defines the lower breakpoint of the dual-slope operating characteristic. The
BUS ZONE 1 DIF LOW BPNT
percentage bias applied for the restraining current from zero to the value specified as
is given by the
LOW BPNT
LOW SLOPE
setting. This setting needs to be set above the maximum load current. The
can be moved to the AC current
LOW BPNT
under which all the CTs are guaranteed to transform without saturation. This includes the effect of residual magnetism.
When adjusting this setting, keep in mind that the restraining signal is created as the maximum of all the input currents.
— This setting defines the percentage bias for the restraining currents above the higher
BUS ZONE 1 DIF HIGH SLOPE
breakpoint (
). This setting affects stability of the relay for heavy external faults. Traditionally, the value chosen for
HIGH BPNT
this setting needs to be high enough to accommodate the spurious differential current resulting from saturation of the CTs
during heavy external faults. This requirement can be considerably relaxed in favor of sensitivity and speed of operation as
the relay detects CT saturation and upon detection applies the directional principle to prevent maloperation. When
adjusting this setting, keep in mind that the restraining signal is created as the maximum of all the input currents.
— This setting defines the higher breakpoint of the dual-slope operating characteristic. The
BUS ZONE 1 DIF HIGH BPNT
percentage bias applied for the restraining current above the value specified as
is given by the
HIGH BPNT
HIGH SLOPE
setting. The
setting needs to be set below the minimum AC current that is likely to saturate the weakest CT
HIGH BPNT
feeding the relay. When adjusting this setting, it must be kept in that mind the restraining signal is created as the
maximum of all the input currents.
The dual-slope operating characteristic of the biased bus differential protection element is shaped to ensure true
percentage bias for high restraining currents (see the following figure). This means that the straight line defining the upper
slope intersects the origin of the differential-restraining plane and a discontinuity appears between the low and high slope
regions (between the
and
settings). This discontinuity is handled by approximating the operate/no-
LOW BPNT
HIGH BPNT
operate boundary of the characteristic using a certain "gluing" function. This ensures smooth transition of the slope from
5
(lower value) to
(higher value).
LOW SLOPE
HIGH SLOPE
The following parameters of the biased operating characteristic are used by the saturation detector:
,
LOW SLOPE
HIGH
, and
. The saturation detector uses these settings to detect specific relations between the differential and
SLOPE
HIGH BPNT
restraining currents. The values of these settings are selected based on the aforementioned criteria related to the art of
bus differential protection.
— This setting defines the minimum differential current required for operation of the unbiased bus
BUS ZONE 1 DIF HIGH SET
differential protection function. This setting is based on the maximum magnitude of the differential current that might be
seen during heavy external faults causing deep CT saturation. When selecting this setting, keep in mind that the unbiased
bus differential protection function uses the full-cycle Fourier measuring algorithm and applies it to pre-filtered samples of
the input currents. As a result, the transient measuring errors including the effect of the DC component are below 2%.
During heavy CT saturation when the currents are significantly distorted, the magnitude of the differential current as
measured by the relay and used by the unbiased bus differential function is significantly lower than both the peak values
of the waveform and the true RMS value. The measured magnitude practically reflects the power system frequency
component alone. This allows for lower values of the
setting.
HIGH SET
The unbiased (high set) differential function can be virtually disabled by setting its operating threshold,
, very high.
HIGH SET
— This setting defines the drop-out time of the seal-in timer applied to the
FlexLogic
BUS ZONE 1 DIF SEAL-IN
BUS 1 OP
operand.
More information on the bus zone differential settings can be found in the Application of Settings chapter.
5-170
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL

Advertisement

Table of Contents
loading

Table of Contents